dc.description.abstract |
In this paper Intelligent Electronic Devices (IED)
that use ethernet for communicating with substation devices on
the grid where modelled in OPNET. There is a need to test the
communication protocol performance over the network. A
model for the substation communication network was
implemented in OPNET. This was done for ESKOM, which is
the electrical power generation and distribution authority in
South Africa. The substation communication model consists of
10 ethernet nodes which simulate protection Intelligent
Electronic Devices (IEDs), 13 ethernet switches, a server which
simulates the substation Remote Terminal Unit (RTU) and the
DNP3 Protocol over TCP/IP simulated on the model. DNP3 is a
protocol that can be used in a power utility computer network
to provide communication service for the grid components. It
was selected as the communication protocol because it is widely
used in the energy sector in South Africa. The network load and
packet delay parameters were sampled when 10%, 50%, 90%
and 100% of devices are online. Analysis of the results showed
that with an increase in number of nodes there was an increase
in packet delay as well as the network load. The load on the
network should be taken into consideration when designing a
substation communication network that requires a quick
response such as a smart gird. |
en |
dc.description.sponsorship |
University of South Africa |
en |
dc.language.iso |
en |
en |
dc.publisher |
IEEE |
en |
dc.subject |
Distributed Network Protocol (DNP3) |
en |
dc.subject |
Intelligent Electronic Devices (IED’s) |
en |
dc.subject |
Network load |
en |
dc.subject |
Packet delay |
en |
dc.subject |
Substation Network Model |
en |
dc.title |
Packet Analysis of DNP3 protocol over TCP/IP at an Electrical Substation Grid modelled in OPNET |